DYZ1-63C

Main Part No.: DYZ1-63C/B60.S

Contact type: Bi-stable

Rated load current of contact(Resistive load): 63A×80V DC

Contact voltage drop:  ≤40mV@63A

Insulation resistance: Min. 100MΩ at 500VDC

Dielectric strength (Between Insulated Electric Parts): 1500VAC 50 HZ/60 HZ (1 minute)  Leak current<1mA

Contact Now >> Donwload
SPECIFICATIONS

■DYZ1-63C Series

 

■Contactor Data 

 

Main Part No.

DYZ1-63C/B60.S

Contact type

Bi-stable

Rated load current of contact

(Resistive load)

63A×80V DC

Contact voltage drop

 ≤40mV@63A

Insulation resistance

Min. 100MΩ at 500VDC

Dielectric strength 

(Between Insulated Electric Parts)

1500VAC 50 HZ/60 HZ (1 minute)  

Leak current<1mA

Vibration

(10~200)HZ、≤3.5g

Shock

(60~100)ops/minute、≤4g

Lightning stroke

8/20us  10/20KA  lightning test ±5 times each

Pollution level

III

Working duty

Continuous

 

■Coil Data

 

P/N

Coil voltage

Coil operating voltage(V)

Pick-up voltage(V)

Drop-out voltage(V)

Start power(A)

Coil Power(W)

DYZ1-63C

60V

36~72

≤42

≤42

≤0.4

≤24

48V

28.8~57.6

≤33.6

≤33.6

≤0.5

24V

14.4~28.8

≤16.8

≤16.8

≤1

12V

7.2~14.4

≤8.4

≤8.4

≤2

 

■Part Numbering System  

Example: DYZ1-63 - c/B60. S. indicates Magnetic latching DC contactor, rated current at DC-1 load is 63A, coil voltage is DC60V.Products with magnetic blowing, with auxiliary contact.

 

■Shape installation and circuit diagram   (Unit: mm)

DYZ1-63C/□.S

Dimension(mm)

Tolerance grade not noted(mm)

0~30

±0.3

30~60

±0.5

60~100

±1

>100

±2

 

Note:

 

1. Main circuit connects copper bus bar which is silver plated;

2. Auxiliary contact connecting plate is silver plated;

3. The product coil has positive and negative pulse excitation, excitation time 50ms≤ T ≤200s.The coil shall not be continuously energized for long periods, the operating frequency shall not exceed 6 times per minute, and the pulse shall be square wave. Positive pulse (" + "is connected to the power supply positive," - "is connected to the power supply negative) makes the contact pick-up, negative pulse (" +" is connected to the power supply negative, "-" is connected to the power supply positive) makes the contact drop-out. After the coil is de-excited, the state of the contactor is maintained in permanent magnetic.

Hot Products
Contact Us for All Your Needs
Our professional team will be online to provide you with the most suitable products for you.
Contact Us

GET A QUOTE

GET IN TOUCH NOW
×
We value your privacy
We use cookies to provide you with a better online experience, analyse and measure website usage, and assist in our marketing efforts.
Accept All