DYZ1-25C

Main Part No.: DYZ1-25C/2ZB□

Contact type: Bi-stable

Rated load current of contact(Resistive load): 25A×410V  DC-1

Contact voltage drop: ≤40mV@25A

Insulation resistance: Min. 100MΩ at 500VDC

Contact Now >> Donwload
SPECIFICATIONS

■DYZ1-25C SERIES

 

■Contactor Data

 

Main Part No.

DYZ1-25C/2ZB□

Contact type

Bi-stable

Rated load current of contact

(Resistive load)

25A×410V  DC-1

Contact voltage drop

≤40mV@25A

Insulation resistance

Min. 100MΩ at 500VDC

Dielectric strength 

(Between Insulated Electric Parts)

1500VAC 50 HZ/60 HZ (1 minute)  

Leak current<1mA

Vibration

(10~200)HZ、≤3.5g

Shock

(60~100)ops/minute、≤4g

Pollution level

III

Working duty

Continuous

 

■Coil Data

 

Model

Coil voltage

Coil operating voltage(V)

Pick-up voltage(V)

Drop-out voltage(V)

Start power

(A)

Coil Power(W)

DYZ1-25C/2ZB□

12V

0.85US~1.1US

20%~80%

20%~80%

≤5

50~80

24V

≤2.5

48V

≤1.25

60V

≤1

72V

≤0.8

 

■Part Numbering System  

Example: DYZ1-25C/2ZB24; indicates DPDT changeover Magnetic latching DC contactor, rated current at DC-1 load is 25A, coil voltage is DC24V.Products with magnetic blowing.

 

■Shape installation and circuit diagram   (Unit: mm)

 

DYZ1-25C/2ZB□

Dimension(mm)

Tolerance grade not noted(mm)

0~30

±0.3

30~60

±0.5

60~100

±1

>100

±2

 

NOTE:

 

1. All the leading foot ends are hanging tin;

2. The product coil adopts pulse excitation, and the excitation time is 200ms≤ T ≤500ms each time.The coil shall not be continuously energized for long periods, the operating frequency shall not exceed 6 times per minute, and the pulse shall be square wave.When "X1+" and "X1-" are connected to "+" and "X1-" are connected to "-", "A1-A1" and "B1-B1" contacts close, "A2-A2" and "B2-B2" contacts are disconnected. After coil excitation, the contact state of the contactor is maintained by the permanent magnetic steel in the product. When "X2+" and "X2-" connect "+" and "X2-" connect "-", the "A1-A1" and "B1-B1" contacts are disconnected, and the "A2-A2" and "B2-B2" contacts are closed. After the coil is de-excited, the contact state of the contactor is maintained by the permanent magnetic steel in the product.