BD Circuit Breaker for Equipment

2.1 Standards : IEC 60947-2、GB14048.2、UL1077、UL489、UL489A
2.2 Rated working voltage: DC80V、DC125V、DC250V、AC120/240V、AC230/400V、AC277/480V
2.3 Mechanical & Electrical Life:10000/6000(UL489A approved at electrical endurance1000)
2.4 Certificates:CCC、UL、TUV、CE
2.5 Wiring capacity:0.5~25mm²,
parallel connection of 2 poles: ≤35 mm²,
parallel connection of 3poles:≤70 mm²
2.6 Auxiliary switch & Trip Alarm switch:DC125V 1A,AC250V 5A
2.7 Rated Breaking Capacity

Contact Now >> Donwload
SPECIFICATIONS

Circuit Breaker BD series

Application Scope
BD series circuit breaker for equipment (hydraulic-magnetic circuit breaker) is used in the power system with rated current from 0.5A to 63A, parallel connection to 150A, with rated voltage up to AC120/240V、AC230/400V、AC277/480V (50/60Hz) or DC80V、DC125V、DC250V. It provides overload, short circuit protection. It can also be used for infrequent close or open. The application fields are computer and peripheral equipment, industrial automatic control system, telecom equipment, power supply system, UPS, railroad, marine, spacecraft, elevator, portable power supply and so on.

Technical Parameters

Voltage(V)

Rated Current(A)

Poles

Breaking Capacity(kA)

UL

CCC/TUV/CE

UL1077

UL489

UL489A

Icu

Ics

DC80

0.5-63

1,2(series)

10U2

10

10

10

5

15~100

2(Parallel)

10U2

/

10

10

5

50~150

3(Parallel)

10 U2

/

10

10

5

DC125

0.5~63

2(series)

5 U2

/

10

10(1P,2P)

5(1P,2P)

DC250

0.5~15

3(series)

10 U2

/

10

10(2P,3P)

5(2P,3P)

AC120/240

0.5~25

1,2,3

10U2

10

/

/

/

AC240/415

0.5~50

1,2,3,1N,3N

/

/

/

6

3

AC277/480

0.5~25

1,2,3,1+N,

1U1

/

/

/

/

Standard Working Condition
3.1 Ambient temperature::-40℃~+85℃, Avg. temperature of 24 hours: ≤+35℃.
3.2 Altitude:≤2000m
3.3 Relative humidity:The relative humidity of the air does not exceed 50% at the maximum temperature of +40℃. Higher relative humidities may be permitted at lower temperature, e.g. 90% at +20℃.
3.4 Service place should be without explosive media, gas and dust which are corrosive and conductive. The product should be mounted free from rain and snow.
3.5 Pollution degree: 2
3.6 Installation type: Ⅱ

Tripping characteristic
4.1 Tripping Time

Current

Curve

1.05In

1.3 In

1.3*1.05In

1.5 In

2 In

3 In

4 In

6 In

10 In

DI/AI

Not Trip

0.003-0.2

0.003-0.18

0.003-0.06

0.003-0.025

0.003-0.02

0.003-0.02

0.003-0.02

0.003-0.02

DS/AS

Not Trip

8-240

7-200

5-50

2-12

0.09-4

0.006-1.8

0.003-0.03

0.003-0.02

YS/LS

Not Trip

11-300

11-250

8-80

4-25

1.2-8

0.6-3.5

0.1-1.1

0.004-0.3

DM/YM

Not Trip

12-240

11-200

10-65

4.5-20

1.2-7

0.6-3

0.01-1

0.003-0.1

AM/LM

Not Trip

20-600

18-540

15-120

7-40

2.5-12

1-6

0.01-1.8

0.003-0.09

DL/AL

Not Trip

60-1500

58-1200

45-420

20-90

8-40

3.8-20

1-7

0.005-2

LL/YL

Not Trip

60-1500

58-1200

40-360

20-90

6-35

3.5-18

1.2-7

0.1-2

Note:
1)Time unit is second;
2) As Standard, the time listed is tested at the product cold state.

4.2 Tripping Curves

Model and Implication

No.

Series

BD

1

Product code

B:Hydraulic electromagnetic circuit breaker

2

Series Code

D:Maximum 63A

3

Tripping curve

DI:DC Instantaneous DS:DC Short DM:DC Medium; DL:DC Long

AI:AC Instantaneous AS:AC Short AM:AC Medium; AL:AC Long

YS:DC Short,Hi-Inrush YM:DC Medium,Hi-Inrush YL:DC LONG,Hi-Inrush

LS:AC Short,Hi-Inrush LM:AC Medium,Hi-Inrush LL:AC LONG,Hi-Inrush

4

Rated current (A)

0.5~150A

5

Number of poles

1– One Pole(1P or 1N);2 – Two Pole(2P or 2U);3– Three Pole(3P or 3N or 3U)

6

Pole and Connection Type

P: Phase pole only of series (1P or 2P or 3P),

N: With neutral pole of series (1N or 3N),

U: parallel, with parallel connection bar(2U or 3U)

7

Accessory

O:No accessory, A:Auxiliary Switch, T:Trip Alarm;

B: Auxiliary Switch & Trip Alarm;

8

Mounting type

D:57mm Escutcheon; M:57mm Escutcheon with plug-in;

E:45mm Escutcheon; N:45mm Escutcheon with plug-in;

9

Client code

XXXXX 5 or more numbers or letters, different customers with special needs, but does not affect the product certification Using the client code, you can omit the fifth behind the content.

Note:
1)Max rated current for single pole is 63A;
2)Only AC type for 3P+N & 3P products;
3)Rated current for parallel connection of 2 Poles for DC type is 100A,while max 150A for 3 poles parallel connection . AC type products cannot be parallel connected.
4) The models listed are the standard model which can be ordered according to the parameters listed; for nonstandard products, please confirm for the manufacturer.

Dimensions and wiring method
6.1 Outline dimensions
6.1.1 57mm Escutcheon

6.1.2 57mm Escutcheon with plug-in

6.1.3 45mm Escutcheon

6.1.4 45mm Escutcheon with plug-in

6.2 Parallel product appearance size

6.3 Attachment installation size

Packing and depositing
The products should be stored in the warehouse where there are ventilation. The relative humidity there should not exceed 80%, and the ambient temperature there is between -40℃ to +85℃. In addition, there should not be acidic, alkaline and corrosive gas in the air. The products should not be deposited more than 3 years in the above mentioned conditions since the producing date.

Notice
8.1 Do not disassemble the breaker privately.
8.2 Attention to live part when the breaker is energized and avoid touching them.
8.3 Please make sure reliable connection to avoid fault tripping or damage of terminal caused by exceptional heat resulting from unsuitable connection.
8.4 Please maintain the distance of 30mm from the arc jet slot of the product (LINE side) when installation in case there is short circuit breaker due to arc jet.