DC contactor ZLJM-250D

■ FEATURES
·250A Contact Switching capability
·SPST-NO Contact Arrangement
·Max. Coil Power Waste: 15W
·Application:For Electric Control System Of Communication Power Supply、Engineering Machine、Electromotion Forklift、Motor Car、Train、Watercraft and UPS etc.
·UL File No.:E145623

Contact Now >> Donwload
SPECIFICATIONS

ZLJM-D DC Contactor ZLJM-250D
 

Model No.

ZLJM—250D/

Contact Arrangement

1H (SPST-NO)

Contact Material

AgCdO(12)

Contact Rating(at Resistive Load)

250A 80VDC

250A 250VAC

Max. Switching Voltage

80VDC,250VAC

Max. Switching Power

62500VA

Endurance of Over Loading Current(7Ie/10S)

1750A/10S

Coil Rated Voltage

12,24,30,48,60,72,120VDC, etc.

Pick-up Voltage

(40~70)% of coil rated voltage

Drop-out Voltage

(5~30)%V of coil rated voltage

Contact Pressure Drop

At most 30mv when 100A

Insulation Resistance

Min. 100MΩ at 500VDC

Dielectric Strength

(Between Insulated Electric Parts)

1000VAC 50 HZ/60 HZ (1 minute)

Operate Time

Max. 50mSec.

Release Time

Max. 50mSec.

Ambient Temper

-25℃~+60℃

The shocking of fixed point

(10~200)HZ、Acceleration≤3.5g

Shocking

(60~100) time/minute、Acceleration≤4g

Mechanical Life

100,000 Operations (no load)

Electrical Life

50,000 Operations (at rated load)

Mounting Direction

Optional

 