■ FEATURES
·400A Contact Switching capability
·SPST-NO Contact Arrangement
·Max. Coil Power Waste: 15W
·Application:For Electric Control System Of Communication Power Supply、Engineering Machine、Electromotion Forklift、Motor Car、Train、Watercraft and UPS etc.
·UL File No.: E145623
ZJLM-C DC Contactor ZLJM-400C
Model No. |
ZLJM—400C/ |
Contact Material |
AgCdO(12) |
Contact Rating(at Resistive Load) |
400A 80VDC 400A 250VAC |
Max. Switching Voltage |
80VDC,250VAC |
Max. Switching Power |
100000VA |
Endurance of Over Loading Current(7Ie/10S) |
2800A/10S |
Coil Rated Voltage |
12、24、48、60、72、96、120VDC,etc |
Pick-up Voltage |
(20~60)% of coil rated voltage |
Drop-out Voltage |
(20~60)% of coil rated voltage |
Contact Pressure Drop |
At most 30mv when 100A |
Insulation Resistance |
Min. 100MΩ at 500VDC |
Dielectric Strength (Between Insulated Electric Parts) |
1000VAC 50 HZ/60 HZ (1 minute) |
Min. pulse width |
500mS |
Ambient Temper |
-25℃~+60℃ |
Mechanical Life |
100,000 Operations (no load) |
Electrical Life |
10,000 Operations (at rated load) |
Coil current |
No more than 700mA |
Mounting Direction |
Optional |
GET A QUOTE