DC contactor ZLJM-200D 1Z

■ FEATURES
·200A Contact Switching capability
·SPDT Contact Arrangement
·Max. Coil Power Waste: 15W
·Application:For Electric Control System Of Communication Power Supply、Engineering Machine、Electro motion Forklift、Motor Car、Train、Watercraft and UPS etc.
·UL File No. :E145623

Contact Now >> Donwload
SPECIFICATIONS

SBDT & DPDT DC Contactor ZLJM-200D 1Z
 

Model No.

ZLJM—200D/1Z

Contact Arrangement

SPDT

Contact Material

AgCdO

Contact Rating(at Resistive Load)

200A 80VDC

200A 250VAC

Max. Switching Voltage

80VDC,250VAC

Max. Switching Power

50000VA

Endurance of Over Loading Current(7Ie/10S)

1400A/10S

Coil Rated Voltage

(12、24、48、60、120)VDC, etc.

Pick-up Voltage

(40~70) % of coil rated voltage

Drop-out Voltage

(5~30) % of coil rated voltage

Contact Pressure Drop

At most 30mv when 100A

Insulation Resistance

Min. 100MΩ at 500VDC

Dielectric Strength

(Between Insulated Electric Parts)

1000VAC 50 HZ/60 HZ (1 minute)

Operate Time

Max. 50mSec.

Release Time

Max. 50mSec.

Ambient Temper

-25℃~+60℃

The shocking of fixed point

(10~200)HZ、Acceleration≤3.5g

Shocking

(60~100) time/minute、Acceleration≤4g

Mechanical Life

100,000 Operations (no load)

Electrical Life

50,000 Operations (at rated load)

 

Hot Products
Contact Us for All Your Needs
Our professional team will be online to provide you with the most suitable products for you.
Contact Us

GET A QUOTE

GET IN TOUCH NOW
×
We value your privacy
We use cookies to provide you with a better online experience, analyse and measure website usage, and assist in our marketing efforts.
Accept All