■ FEATURES
·100A Contact Switching capability
·SPST-NC Contact Arrangement
·Max. Coil Power Waste:10.5W
·Application:For Electric Control System Of Communication Power Supply、Engineering Machine、Electro-motion Forklift、Motor Car、Train、Watercraft and UPS etc.
·Technique Criterion:GB14048.4-2003
·TUV File No.:50054080
·CCC File No.:2004010304116987
·UL File No.:E145623
BZJ NC DC Contactor BZJ-100D
Model No. |
BZJ—100D/ |
Contact Arrangement |
1D (SPST-NC) |
Contact Material |
AgCdO |
Contact Rating(at Resistive Load) |
100A 48VDC 100A 250VAC |
Max. Switching Voltage |
60VDC,250VAC |
Max. Switching Power |
25000VA |
Endurance of Over Loading Current(7Ie/10S) |
700A/10S |
Coil Rated Voltage |
(12、24、48、60、72、120 )VDC,etc. |
Pick-up Voltage |
(40~70)% of coil rated voltage |
Drop-out Voltage |
(5~30)% of coil rated voltage |
Contact Pressure Drop |
At most 30mV when 100A |
Insulation Resistance |
Min. 100MΩ at 500VDC |
Dielectric Strength (Between Insulated Electric Parts) |
1000VAC 50 HZ/60 HZ (1 minute) |
Operate Time |
Max. 50mSec. |
Release Time |
Max. 50mSec. |
Ambient Temperature |
-40℃~+60℃ |
The shocking of fixed point |
(10~200)HZ、Acceleration≤3.5g |
Shocking |
(60~100) time/minute、Acceleration≤4g |
Mechanical Life |
100,000 Operations (no load) |
Electrical Life |
50,000 Operations (at rated load) |